Rosemount
Contact us
TEL: 001-646-569-9958
FAX: 001-646-569-9958
E-mail: services@myjackwell.com
Add:245 E MAIN ST STE 115,ALHAMBRA CA 91801,USA
Rosemount
Rosemount 0085 Temperature Sensor and Rosemount 644 Temperat
As a trusted supplier, we offer the Rosemount 0085 Pipe Clamp Temperature Sensor and Rosemount 644 Temperature Transmitter, designed for industrial use with high durability and precision. Both products are certified for hazardous environments and ensure reliable performance. With fast shipping, customizable calibration options, and expert technical support, we provide everything you need to meet your temperature measurement requirements.
Brand
Rosemount
Purchase details
Free Online Product Selection Service
Fast Quoting & Competitive pricing
Min. order: 1 piece & 2-Year Warranty
Specification
Rosemount 0085 Pipe Clamp Temperature Sensor Rosemount 644 Temperature Transmitter
Pipe Clamp Materials: ASTM 304 SST (1.4301), Duplex F51 (1.4462), Carbon steel (1.0037)
Input: Dual and single sensor capability with universal sensor inputs (RTD, T/C, mV, ohms)
Input: Dual and single sensor capability with universal sensor inputs (RTD, T/C, mV, ohms)
Lead Wires: PTFE insulated, silver-coated copper wire
Output Signal: 4-20 mA /HART™ protocol, FOUNDATION™ fieldbus protocol, PROFIBUS™ PA protocol
Output Signal: 4-20 mA /HART™ protocol, FOUNDATION™ fieldbus protocol, PROFIBUS™ PA protocol
Insulation Resistance: 1,000 MΩ minimum insulation resistance when measured at 500 V dc at room temperature
Housing: Field mount, DIN A head mount or rail mount
Housing: Field mount, DIN A head mount or rail mount
Calibration Options: Class A Sensor from -50 to 300 °C (-58 to 572 °F)
Display/Interface: LCD Display, LCD Display with Local Operator Interface (LOI), or LED
Display/Interface: LCD Display, LCD Display with Local Operator Interface (LOI), or LED
Certifications/Approvals: Hazardous location, see full specs for complete list of certifications
Diagnostics: Basic diagnostics, Hot Backup™ capability, sensor drift alert, thermocouple degradation, min/max tracking
Diagnostics: Basic diagnostics, Hot Backup™ capability, sensor drift alert, thermocouple degradation, min/max tracking
Calibration Options: Transmitter-sensor matching (Callendar-Van Dusen constants), 5-point calibration
Certifications/Approvals: SIL 2/3 certified to IEC 61508 by an independent 3rd party, hazardous location, marine type, see full specs for complete list of certifications