Part Number: YTA710-FA2A2DB/KF2
Model: YTA710 Temperature Transmitter
Brand: Yokogawa
Condition: New & Original in Factory Packing
Factory Warranty: 12 Months
Overview
The YTA710 provides high accuracy, stability, and reliability. The housing structure adopts reliable dual-compartment structure. The sensor input can be choice of single or dual inputs. This input can accept the RTD, thermocouple, ohm, or DC millivolt. It converts the sensor input to a 4 to 20mA DC analog signal or Fieldbus digital signal. HART 7 Protocol, BRAIN Protocol or FOUNDATION™ Fieldbus ITK 6 version are available. The dual input can accept two sensors calculation of the differential or average value and the sensor backup function. Sensor backup functions for automatically switches-over from the primary to the backup upon sensor failure.
By adoption of local parameter switch on the Indicator, it becomes easy to do the on-site setting work.
YTA710 features include:
- Dual-compartment field-mount housing
- Choice of HART 7, BRAIN Protocol or FOUNDATION Fieldbus ITK 6 Protocol
- Local Parameter Setting function (Indicator model)
- Advanced diagnosis
Ordering Information
Model | YTA710 | Temperature Transmitter |
Output signal | -F | Digital communication (FOUNDATION Fieldbus protocol) |
A | Always A (Global) | |
Sensor input | 2 | Double |
Housing code | A | Aluminum |
Electrical connection | 2 | 1/2 NPT female |
Integral indicator | D | Digital indicator with Local Operating Switch |
Mounting bracket | B | 304 SST or ASTM304L stainless steel 2-inch horizontal pipe mounting bracket(1) |
ATEX | /KF2 |
[4-20mA & Fieldbus: Flameproof and dust ignition proof approval] Applicable Standard: EN IEC 60079-0, EN 60079-1, EN 60079-31 Certificate: KEMA 07ATEX0130X II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex tb IIIC T70°C/T90°C Db Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5 Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C Enclosure: IP66/IP67 Electrical Connection: 1/2 NPT female and M20 female(2) |
- For flat-panel mounting, please prepare bolts and nuts.
- Applicable for Electrical Connection Code 2 and 4.
NOTE: This item is a replacement of YTA320-FA2DB/KF2
- Estimated Lead Time: 6 – 8 Weeks
- Shipping Weight: 5 Kg